Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 13, 2020, 08:29 AM
  • 08 0224_08 0223A_07132020_014403.mp4

Date
07/13/2020
W/O
839004
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00005
PipeID
P00098
Time
1:29 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7912
Sewer Name
EAST ROAD TRUNK
City
TORRANCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_839004_TV08112_JUL2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
08 0224
Downstream MH
08 0223A
Dir. of Survey
Downstream
Length Surveyed
279 ft.
Total Length
279 ft.
Structural Index
3
Structural Quick
413J
Structural Rating
276
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
276
Pipe schematic from manhole 08 0224 to 08 0223A
MH: 08 0224MH: 08 0223Adownstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 02240.1 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start4.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.6 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK45.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"97.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"148.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"195.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"246.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"274.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish274.8 ft. FM - Fracture Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES275 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish279 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK279 ft. AMH - Downstream Manhole, Survey Ends - 08 0223A

Observation photos (2)

  • General Observation - CONNECTION AT MH 3 O'CLOCK

    4.6 ft. - General Observation - CONNECTION AT MH 3 O'CLOCK

  • Fracture Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES

    274.8 ft. - Fracture Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
195.6TFC
4.5CM
0.1MWM
97.6TFC
275SSS
2SSS
0MWL
246.1TFC
279MGOCONNECTION AT MH 9 O'CLOCK
274.8CM
45.5TFC
279AMH08 0223A
4.6MGOCONNECTION AT MH 3 O'CLOCK
148.5TF
274.8FM
0AMH08 0224

Properties (7)

additional_info
SC411771
custom_field_three
POSSIBLE DEFECTIVE VCP
custom_field_two
2
customer
1
datetime
2020-07-13T01:29:04-07:00
documentation
PROPIPE
is_lateral_inspection
false