Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 10, 2020, 07:38 AM
  • 08 0216_08 0215 _07102020_004241.mp4

Date
07/10/2020
W/O
839004
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00005
PipeID
P00086
Time
12:38 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7911
Sewer Name
EAST ROAD TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_839004_TV08112_JUL2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
08 0216
Downstream MH
08 0215
Dir. of Survey
Downstream
Length Surveyed
43.1 ft.
Total Length
43.1 ft.
Structural Index
3
Structural Quick
4738
Structural Rating
68
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
68
Pipe schematic from manhole 08 0216 to 08 0215
MH: 08 0216MH: 08 0215downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK CAPPED0 ft. AMH - Upstream Manhole, Survey Begins - 08 02162 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - POSSIBLE DEFECTIVE VCP3.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start42 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish43.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK43.1 ft. AMH - Downstream Manhole, Survey Ends - 08 021543.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish43.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0MWL
0MGOCONNECTION AT MH 9 O'CLOCK CAPPED
0MWM
0MGOCONNECTION AT MH 3 O'CLOCK CAPPED
43.1MGOCONNECTION AT MH 3 O'CLOCK
3.3CM
43.1AMH08 0215
7FM
43.1FM
42SSS
0AMH08 0216
2SSSPOSSIBLE DEFECTIVE VCP
43.1CM

Properties (7)

additional_info
SC411770
custom_field_three
POSSIBLE DEFECTIVE VCP
custom_field_two
2
customer
1
datetime
2020-07-10T00:38:06-07:00
documentation
PROPIPE
is_lateral_inspection
false