Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 9, 2020, 08:07 AM
  • 08 0282_08 0613_07092020_011127.mp4

Date
07/09/2020
W/O
839310
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00011
PipeID
P00652
Time
1:07 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7907
Sewer Name
JAMES STREET RELIEF TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
07
Purpose
Routine Assessment
Project
WO_839310_TV08147_JUL2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
24 in.
Upstream MH
08 0613
Downstream MH
08 0282
Dir. of Survey
Upstream
Length Surveyed
80.9 ft.
Total Length
80.9 ft.
Structural Index
2
Structural Quick
2B00
Structural Rating
30
O&M Index
2
O&M Quick
2B00
O&M Rating
30
Overall Index
2
Overall Quick
Overall Rating
60
Pipe schematic from manhole 08 0613 to 08 0282
MH: 08 0613MH: 08 0282upstream0 ft. MGO - General Observation - CONN @ MH 11 O'CLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Ends - 08 02820 ft. MGO - General Observation - CONN @ MH 1 O'CLOCK/ACTIVE2.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish78.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start78.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start80.9 ft. MWM - Water Mark, 20 %of cross sectional area80.9 ft. AMH - Downstream Manhole, Survey Begins - 08 061380.9 ft. MWL - Water Level, 15 %of cross sectional area80.9 ft. MGO - General Observation - ROACHES @ MH

Observations (11)

DistanceCodeObservation
80.9MGOCONN @ MH 11 O'CLOCK/ACTIVE
80.9AMH08 0282
0MWM
78SSS
0AMH08 0613
80.9MGOCONN @ MH 1 O'CLOCK/ACTIVE
2DAGS
0MWL
2SSS
0MGOROACHES @ MH
78DAGS

Properties (7)

additional_info
SC411765
custom_field_two
3
customer
1
datetime
2020-07-09T01:07:05-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
30711