Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 30, 2020, 05:36 AM
  • 02 1464_02 1463 _07292020_225533.mp4

Date
07/29/2020
W/O
844577
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00309
PipeID
P03908
Time
10:36 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7890
Sewer Name
UNION PACIFIC TRUNK
City
COMMERCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_844577_TV02355_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
24 in.
Upstream MH
02 1464
Downstream MH
02 1463
Dir. of Survey
Downstream
Length Surveyed
313.6 ft.
Total Length
313.6 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
162
O&M Index
2
O&M Quick
2K00
O&M Rating
124
Overall Index
2
Overall Quick
Overall Rating
286
Pipe schematic from manhole 02 1464 to 02 1463
MH: 02 1464MH: 02 1463downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 14642 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start39.7 ft. CM - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES, Start81.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"84.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"99.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start99.7 ft. CM - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES, Finish106 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"109.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"135.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, Unknown Status - NOT OBSERVED INTERNALLY - PASSED-BY139.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6" - CRACKED CAP158.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"161.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"179.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"182.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"207.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"210.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"234.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"237.4 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"259 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"261.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"283.2 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"286.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"307.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"310.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"311.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish311.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish311.9 ft. MGO - General Observation - COCKROACHES AT MH313.6 ft. AMH - Downstream Manhole, Survey Ends - 02 1463313.6 ft. MGO - General Observation - ACTIVE DROP CONNECTION IN MH, 4 O' CLOCK

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES, Start

    39.7 ft. - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    99.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES AT MH

    311.9 ft. - General Observation - COCKROACHES AT MH

Observations (32)

DistanceCodeObservation
311.9CM
161.2TFC
261.3TFC
139.7TFCCRACKED CAP
313.6AMH02 1463
237.4TF
283.2TF
81.7TFC
310.3TFC
39.7CM
84.4TFA
0MWM
286.1TFC
313.6MGOACTIVE DROP CONNECTION IN MH, 4 O' CLOCK
259TFC
179.8TFC
311.9DAGS
182.7TFC
311.9MGOCOCKROACHES AT MH
158.4TFC
210.3TFC
234.4TFC
106TFC
99.7CM
2DAGS
0MWL
109.5TFC
99.7CM
0AMH02 1464
135.5TFNOT OBSERVED INTERNALLY - PASSED-BY
307.7TFC
207.1TFC

Properties (7)

additional_info
SC411730
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2020-07-29T22:36:48-07:00
documentation
PRO PIPE
is_lateral_inspection
false