Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 14, 2020, 07:36 AM
  • 15 0419_15 0934_08142020_010123.mp4

Date
08/14/2020
W/O
844697
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00607
PipeID
P12345
Time
12:36 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7956
Sewer Name
HILL DRIVE EXTENSION TRUNK
City
SOUTH SAN GABRIEL
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
27
Purpose
Routine Assessment
Project
RFIR_WO_844697_TV15221_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0419
Downstream MH
15 0934
Dir. of Survey
Downstream
Length Surveyed
284.3 ft.
Total Length
284.3 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
159
O&M Index
2
O&M Quick
5131
O&M Rating
120
Overall Index
3
Overall Quick
Overall Rating
279
Pipe schematic from manhole 15 0419 to 15 0934
MH: 15 0419MH: 15 0934downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 04190 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MWM - Water Mark, 75 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start19.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start69.3 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"79.1 ft. RMJ - Roots Medium Joint, from 03 to 09 o'clock, 25 %, within 8 inches of joint: YESR84.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"107.9 ft. MWL - Water Level, 20 %of cross sectional area167.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"180.2 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"254.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"271.6 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"282.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish282.9 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish284.3 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK284.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE284.3 ft. AMH - Downstream Manhole, Survey Ends - 15 0934

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    19.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Joint, from 03 to 09 o'clock, 25 %, within 8 inches of joint: YESR

    79.1 ft. - Roots Medium Joint, from 03 to 09 o'clock, 25 %, within 8 inches of joint: YESR

  • General Observation - COCKROACHES IN MANHOLE

    284.3 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (19)

DistanceCodeObservation
0AMH15 0419
282.9CM
84.5TFC
2DAGS
79.1RMJ
284.3MGOCONNECTION AT MH 3 O'CLOCK
180.2TBA
0MWL
284.3MGOCOCKROACHES IN MANHOLE
0MWM
282.9DAGS
0MGOCOCKROACHES IN MANHOLE
254.4TFA
271.6TBA
284.3AMH15 0934
107.9MWL
69.3TBA
167.6TFC
19.4CM

Properties (7)

additional_info
SC411746
custom_field_three
MULTIPLE CRACKS/MEDIUM ROOTS
custom_field_two
2
customer
1
datetime
2020-08-14T00:36:06-07:00
documentation
PRO PIPE
is_lateral_inspection
false