Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 6, 2020, 09:54 AM
  • 20 0291_20 0290_07062020_030259.mp4

Date
07/06/2020
W/O
833690
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00751
PipeID
P19257
Time
2:54 AM
Certificate
U-111-11880
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7866
Sewer Name
20TH STREET EAST RELIEF TRUNK
City
PALMDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 20
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_833690_TV20025_JUN2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
20 0291
Downstream MH
20 0290
Dir. of Survey
Downstream
Length Surveyed
196.6 ft.
Total Length
196.6 ft.
Structural Index
3
Structural Quick
3G00
Structural Rating
117
O&M Index
2
O&M Quick
2G11
O&M Rating
79
Overall Index
2
Overall Quick
Overall Rating
196
Pipe schematic from manhole 20 0291 to 20 0290
MH: 20 0291MH: 20 0290downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 20 02910 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"66.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"66.5 ft. RFC - Roots Fine Connection, from 01 to 03 o'clock, within 8 inches of joint: YES99.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"123.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"131.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"183.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"187.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"194.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish194.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish196.6 ft. AMH - Downstream Manhole, Survey Ends - 20 0290

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Connection, from 01 to 03 o'clock, within 8 inches of joint: YES

    66.5 ft. - Roots Fine Connection, from 01 to 03 o'clock, within 8 inches of joint: YES

Observations (17)

DistanceCodeObservation
0MGOCONNECTION AT MH 9 O'CLOCK
0MWL
131.3TFC
0AMH20 0291
183.9TFA
2DAGS
123.2TFA
194.8SAP
194.8DAGS
196.6AMH20 0290
66.5TFA
2SAP
0MWM
10.2TFA
99.1TFC
66.5RFC
187.9TFA

Properties (6)

additional_info
SC411705
custom_field_two
3
customer
1
datetime
2020-07-06T02:54:02-07:00
documentation
PRO PIPE
is_lateral_inspection