Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 15, 2020, 09:34 AM
  • 03 0147_03 0146A_07152020_024302.mp4

Date
07/15/2020
W/O
838910
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00363
PipeID
P04764
Time
2:34 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7919
Sewer Name
LAKEWOOD TRUNK
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_838910_TV03169_JUL2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
24 in.
Upstream MH
03 0146A
Downstream MH
03 0147
Dir. of Survey
Upstream
Length Surveyed
163.1 ft.
Total Length
163.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 03 0146A to 03 0147
MH: 03 0146AMH: 03 0147upstream0 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 03 01475 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES89.9 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"160.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start163.1 ft. AMH - Downstream Manhole, Survey Begins - 03 0146A163.1 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK163.1 ft. MWL - Water Level, 20 %of cross sectional area163.1 ft. MWM - Water Mark, 25 %of cross sectional area

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    73.2 ft. - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    158.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

Observations (10)

DistanceCodeObservation
0AMH03 0146A
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
163.1CM
163.1MGOACTIVE CONNECTION AT MH 9 O'CLOCK
163.1AMH03 0147
73.2TBA
0MWL
158.1DAGS
0MWM
2.7CM

Properties (7)

additional_info
SC411778
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-07-15T02:34:03-07:00
documentation
PROPIPE
is_lateral_inspection
false