Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 27, 2020, 11:42 AM
  • 18 0986_18 0985_8272020_044648.mp4

Date
08/27/2020
W/O
0844905
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00717
PipeID
P14837
Time
4:42 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1549R
Sewer Name
18 WORSHAM CREEK RELIEF TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
11
Purpose
Maintenance Related
Project
20200827MDM_WORSHAM_CREEK_RELIEF_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
18 0985
Downstream MH
18 0986
Dir. of Survey
Upstream
Length Surveyed
45.8 ft.
Total Length
45.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
4
O&M Quick
4131
O&M Rating
7
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole 18 0985 to 18 0986
MH: 18 0985MH: 18 0986upstream0 ft. RBJ - Roots Ball Joint, from 07 to 05 o'clock, 85 %, within 8 inches of joint: YESR - (XX)0 ft. MSA - Survey Abandoned - 85% ROOTS14.7 ft. RMJ - Roots Medium Joint, from 07 to 10 o'clock, 25 %, within 8 inches of joint: YESR - (XX)45.8 ft. AMH - Downstream Manhole, Survey Begins - 4:45AM45.8 ft. MWM - Water Mark, 20 %of cross sectional area45.8 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (2)

  • Roots Medium Joint, from 07 to 10 o'clock, 25 %, within 8 inches of joint: YESR - (XX)

    31.1 ft. - Roots Medium Joint, from 07 to 10 o'clock, 25 %, within 8 inches of joint: YESR - (XX)

  • Roots Ball Joint, from 07 to 05 o'clock, 85 %, within 8 inches of joint: YESR - (XX)

    45.8 ft. - Roots Ball Joint, from 07 to 05 o'clock, 85 %, within 8 inches of joint: YESR - (XX)

Observations (6)

DistanceCodeObservation
0AMH4:45AM
45.8RBJ(XX)
31.1RMJ(XX)
45.8MSA85% ROOTS
0MWM
0MWL

Properties (5)

additional_info
ROOT EVALUATION ONLY
customer
LACSD
datetime
2020-08-27T04:42:11-07:00
documentation
MARTIN,OLIVER 111,CASTILLO
is_lateral_inspection
false