Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 14, 2020, 05:50 AM
  • 02 1788_02 2411 _07132020_232210.mp4

Date
07/13/2020
W/O
838906
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00274
PipeID
P21173
Time
10:50 PM
Certificate
U-715-070007770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7829
Sewer Name
INDIANA STREET P.P. CONNECTIONS
City
E. LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
07A
Purpose
Routine Assessment
Project
RFIR_WO_838906_TV02400_JUL2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1788
Downstream MH
02 2411
Dir. of Survey
Downstream
Length Surveyed
452.3 ft.
Total Length
452.3 ft.
Structural Index
4
Structural Quick
4O00
Structural Rating
324
O&M Index
2
O&M Quick
2Q00
O&M Rating
178
Overall Index
3
Overall Quick
Overall Rating
502
Pipe schematic from manhole 02 1788 to 02 2411
MH: 02 1788MH: 02 2411downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 17880 ft. MWM - Water Mark, 15 %of cross sectional area7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start44.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start451.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish451.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish452 ft. MGO - General Observation - ACTIVE CONNECTION @ D/S MH - 12 O'CLK - "BACK WALL"452.3 ft. AMH - Downstream Manhole, Survey Ends - 02 2411

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    44.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MWL
451.8DAGS
44.9FM
452MGOACTIVE CONNECTION @ D/S MH - 12 O'CLK - "BACK WALL"
0AMH02 1788
451.8FM
452.3AMH02 2411
7DAGS
0MWM

Properties (7)

additional_info
SC411639
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2020-07-13T22:50:00-07:00
documentation
PROPIPE
is_lateral_inspection
false