Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 13, 2020, 08:57 AM
  • G 0324_G 0323_07132020_021735.mp4

Date
07/13/2020
W/O
838752
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01247
PipeID
P01760
Time
1:57 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7828
Sewer Name
G JOINT OUTFALL G - UNIT 9 TRUNK
City
SOUTH GATE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_838752_TV01202_JUL2020
Sewer Type
Gravity
Material
RCP-CTL
Shape
Circular
Height
30 in.
Width
39 in.
Upstream MH
G 0324
Downstream MH
G 0323
Dir. of Survey
Downstream
Length Surveyed
206.7 ft.
Total Length
206.7 ft.
Structural Index
3
Structural Quick
3G00
Structural Rating
114
O&M Index
3
O&M Quick
413G
O&M Rating
124
Overall Index
3
Overall Quick
Overall Rating
238
Pipe schematic from manhole G 0324 to G 0323
MH: G 0324MH: G 0323downstream0 ft. MGO - Reversal Inspection0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - G 03240 ft. MWM - Water Mark, 55 %of cross sectional area3.7 ft. MGO - General Observation - MAG COATING8.1 ft. DSC - Deposits Settled Compacted, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - POSSIBLE TILES15.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start23.3 ft. MGO - General Observation - CAMERA UNSTABLE DUE TO DEBRIS34.7 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MISSING TILES206.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish206.7 ft. DSC - Deposits Settled Compacted, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish206.7 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - MISSING TILES206.7 ft. MSA - Survey Abandoned - REVERSAL COMPLETED

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    15.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MISSING TILES

    34.7 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MISSING TILES

Observations (14)

DistanceCodeObservation
23.3MGOCAMERA UNSTABLE DUE TO DEBRIS
206.7SAP
0MGO
206.7DSC
0MWL
15.9SAP
206.7SZMISSING TILES
8.1DSCPOSSIBLE TILES
34.7SZMISSING TILES
206.7MSAREVERSAL COMPLETED
0MGOCONNECTION AT MH, 3 O'CLOCK
3.7MGOMAG COATING
0AMHG 0324
0MWM

Properties (8)

additional_info
SC411638
custom_field_three
MISSING TILES, AGGREGATE PROJECING
custom_field_two
2
customer
1
datetime
2020-07-13T01:57:05-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
10286