Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 13, 2020, 08:30 AM
  • G 0326_G 0325_07132020_015131.mp4

Date
07/13/2020
W/O
838752
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01247
PipeID
P01762
Time
1:30 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7828
Sewer Name
G JOINT OUTFALL G - UNIT 9 TRUNK
City
SOUTH GATE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_838752_TV01202_JUL2020
Sewer Type
Gravity
Material
RCP-CTL
Shape
Circular
Height
30 in.
Width
39 in.
Upstream MH
G 0325
Downstream MH
G 0326
Dir. of Survey
Upstream
Length Surveyed
19.3 ft.
Total Length
19.3 ft.
Structural Index
3
Structural Quick
3300
Structural Rating
9
O&M Index
3
O&M Quick
4123
O&M Rating
10
Overall Index
3
Overall Quick
Overall Rating
19
Pipe schematic from manhole G 0325 to G 0326
MH: G 0325MH: G 0326upstream0 ft. MSA - Survey Abandoned - HEAVY DEBRIS0 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - MISSING TILES0 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0.4 ft. MGO - General Observation - CAMERA UNSTABLE DUE TO DEBRIS13.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start14 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MISSING TILES14.6 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - POSSIBLY TILES15.1 ft. MGO - General Observation - MAG COATING ATTATCHED19.3 ft. MGO - General Observation - CONNECTION AT MH, 3 AND 9 O'CLOCK19.3 ft. MGO - Reversal Inspection19.3 ft. MWM - Water Mark, 50 %of cross sectional area19.3 ft. AMH - Downstream Manhole, Survey Begins - G 032519.3 ft. MWL - Water Level, 30 %of cross sectional area

Observation photos (2)

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MISSING TILES

    5.3 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MISSING TILES

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
4.7DSCPOSSIBLY TILES
19.3MSAHEAVY DEBRIS
0MGOCONNECTION AT MH, 3 AND 9 O'CLOCK
5.3SZMISSING TILES
18.9MGOCAMERA UNSTABLE DUE TO DEBRIS
4.2MGOMAG COATING ATTATCHED
19.3SZMISSING TILES
19.3DSC
0MGO
0MWM
5.4SAP
0AMHG 0325
19.3SAP
0MWL

Properties (8)

additional_info
SC411638
custom_field_three
MSA, DEBRIS
custom_field_two
5
customer
1
datetime
2020-07-13T01:30:00-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
10286