Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 10, 2020, 07:54 AM
  • G 0332_G 0331_07102020_010650.mp4

Date
07/10/2020
W/O
838752
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01247
PipeID
P01768
Time
12:54 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7827
Sewer Name
G JOINT OUTFALL G - UNIT 9 TRUNK
City
SOUTH GATE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_838752_TV01202_JUL2020
Sewer Type
Gravity
Material
RCP-CTL
Shape
Circular
Height
30 in.
Width
36 in.
Upstream MH
G 0331
Downstream MH
G 0332
Dir. of Survey
Upstream
Length Surveyed
253.5 ft.
Total Length
253.5 ft.
Structural Index
4
Structural Quick
4100
Structural Rating
4
O&M Index
2
O&M Quick
2F00
O&M Rating
66
Overall Index
2
Overall Quick
Overall Rating
70
Pipe schematic from manhole G 0331 to G 0332
MH: G 0331MH: G 0332upstream0 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - G 03320 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: NO - AT MOUTH OF PIPE0 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish162.5 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - DEBRIS251.1 ft. MGO - General Observation - MAG COATING ATTATCHED253.5 ft. MWM - Water Mark, 15 %of cross sectional area253.5 ft. MWL - Water Level, 10 %of cross sectional area253.5 ft. AMH - Downstream Manhole, Survey Begins - G 0331

Observation photos (2)

  • Deposits Settled Compacted,  10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start - DEBRIS

    91 ft. - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - DEBRIS

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: NO - AT MOUTH OF PIPE

    253.5 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: NO - AT MOUTH OF PIPE

Observations (10)

DistanceCodeObservation
253.5MGOCONNECTION AT MH, 3 O'CLOCK
0MWM
2.4MGOMAG COATING ATTATCHED
253.5MGOCONNECTION AT MH, 9 O'CLOCK
253.5AMHG 0332
253.5FMAT MOUTH OF PIPE
91DSCDEBRIS
253.5DSC
0MWL
0AMHG 0331

Properties (8)

additional_info
SC411637
custom_field_three
FRACTURED
custom_field_two
3
customer
1
datetime
2020-07-10T00:54:08-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
10286