- Date
- 07/09/2020
- W/O
- 838752
- Weather
- Dry
- Operator/Surveyor
- J. BUENROSTRO
- Sewer ID
- Z01247
- PipeID
- P01765
- Time
- 10:58 PM
- Certificate
- U-715-07000770
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K7827
- Sewer Name
- G JOINT OUTFALL G - UNIT 9 TRUNK
- City
- SOUTH GATE
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 11
- Purpose
- Routine Assessment
- Project
- RFIR_WO_838752_TV01202_JUL2020
- Sewer Type
- Gravity
- Material
- RCP-CTL
- Shape
- Circular
- Height
- 30 in.
- Width
- 39 in.
- Upstream MH
- G 0329
- Downstream MH
- G 0328
- Dir. of Survey
- Downstream
- Length Surveyed
- 258.6 ft.
- Total Length
- 258.6 ft.
- Structural Index
- 2
- Structural Quick
- 2100
- Structural Rating
- 2
- O&M Index
- 2
- O&M Quick
- 392S
- O&M Rating
- 229
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 231
Pipe schematic from manhole G 0329 to G 0328 Observation photos (4)

2.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

6.4 ft. - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

206.5 ft. - Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: NO

212.1 ft. - Deposits Attached Encrustation, 15 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start