Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 10, 2020, 10:08 AM
  • G 0324_G 0323_07102020_031820.mp4

Date
07/10/2020
W/O
838752
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01247
PipeID
P01760
Time
3:08 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7827
Sewer Name
G JOINT OUTFALL G - UNIT 9 TRUNK
City
SOUTH GATE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_838752_TV01202_JUL2020
Sewer Type
Gravity
Material
RCP-CTL
Shape
Circular
Height
30 in.
Width
39 in.
Upstream MH
G 0323
Downstream MH
G 0324
Dir. of Survey
Upstream
Length Surveyed
16.1 ft.
Total Length
16.1 ft.
Structural Index
3
Structural Quick
3400
Structural Rating
12
O&M Index
3
O&M Quick
4132
O&M Rating
10
Overall Index
3
Overall Quick
Overall Rating
22
Pipe schematic from manhole G 0323 to G 0324
MH: G 0323MH: G 0324upstream0 ft. MSA - Survey Abandoned - DEBIS (POSSIBLY TILES)0.1 ft. DSC - Deposits Settled Compacted, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish0.1 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - MISSING TILES0.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.8 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MISSING TILES10.1 ft. MGO - General Observation - CAMERA UNSTABLE DUE TO DEBRIS11.7 ft. DSC - Deposits Settled Compacted, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start12.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start16.1 ft. MWL - Water Level, 45 %of cross sectional area16.1 ft. MWM - Water Mark, 60 %of cross sectional area16.1 ft. AMH - Downstream Manhole, Survey Begins - G 0323

Observation photos (3)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MISSING TILES

    8.3 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MISSING TILES

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
4.4DSC
16DSC
9.1SAP
16CM
0MWL
3.5CM
16.1MSADEBIS (POSSIBLY TILES)
16SZMISSING TILES
0MWM
6MGOCAMERA UNSTABLE DUE TO DEBRIS
0AMHG 0323
8.3SZMISSING TILES
16SAP

Properties (6)

additional_info
SC411637
customer
1
datetime
2020-07-10T03:08:11-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
10286