Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 23, 2020, 09:15 AM
  • 15 0732_15 0731_06232020_023457.mp4

Date
06/23/2020
W/O
833716
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00616
PipeID
P12625
Time
2:15 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7804
Sewer Name
15 MONROVIA OUTFALL TRUNK
City
MONROVIA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
09
Purpose
Routine Assessment
Project
WO_833716_TV15131_JUN2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
15 0732
Downstream MH
15 0731
Dir. of Survey
Downstream
Length Surveyed
659.1 ft.
Total Length
659.1 ft.
Structural Index
3
Structural Quick
513Y
Structural Rating
398
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
398
Pipe schematic from manhole 15 0732 to 15 0731
MH: 15 0732MH: 15 0731downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 07320 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. MGO - General Observation - COCKROACHES THROUHOUT SEWER LINE2.4 ft. MGO - General Observation - MAG COATING ATTATCHED10.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4" - ACTIVE12.3 ft. SRV - Surface Reinforcement Visible, at 09 o'clock, within 8 inches of joint: NO151.1 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN STATUS222.6 ft. SRP - Surface Reinforcement Projecting, from 01 to 02 o'clock, within 8 inches of joint: NO250.4 ft. MGO - General Observation - REINFORCEMENT DAMAGED - @ 9 O'CLOCK658.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish659.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0731659.1 ft. MGO - General Observation - CONNECTION IN MH, 3 O' CLOCK

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, at 09 o'clock, within 8 inches of joint: NO

    12.3 ft. - Surface Reinforcement Visible, at 09 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Projecting, from 01 to 02 o'clock, within 8 inches of joint: NO

    222.6 ft. - Surface Reinforcement Projecting, from 01 to 02 o'clock, within 8 inches of joint: NO

Observations (14)

DistanceCodeObservation
0AMH15 0732
659.1AMH15 0731
250.4MGOREINFORCEMENT DAMAGED - @ 9 O'CLOCK
2.4MGOMAG COATING ATTATCHED
222.6SRP
10.1SAP
151.1TBUNKNOWN STATUS
12.3TBACTIVE
12.3SRV
658.3SAP
0MWM
659.1MGOCONNECTION IN MH, 3 O' CLOCK
2MGOCOCKROACHES THROUHOUT SEWER LINE
0MWL

Properties (7)

additional_info
SC411614
custom_field_three
AGGREGATE PROJECTING, REINFORCEMENT PROJECTING
custom_field_two
2
customer
1
datetime
2020-06-23T02:15:49-07:00
documentation
PROPIPE
is_lateral_inspection
false