- Date
- 08/21/2020
- W/O
- 0838782
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00048
- PipeID
- P10331
- Time
- 2:03 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H1543
- Sewer Name
- F JOINT OUTFALL F - UNIT 7F
- City
- CERRITOS
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 38
- Purpose
- Capital Improvement Program Assesment
- Project
- 20200818MDM_JOINT_OUTFALL_UNIT_7F
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 33 in.
- Upstream MH
- F 0201
- Downstream MH
- F 0200
- Dir. of Survey
- Downstream
- Length Surveyed
- 500.9 ft.
- Total Length
- 500.9 ft.
- Structural Index
- 2
- Structural Quick
- 2300
- Structural Rating
- 6
- O&M Index
- 2
- O&M Quick
- 2200
- O&M Rating
- 4
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 10
Pipe schematic from manhole F 0201 to F 0200 Observation photos (5)

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

2 ft. - General Observation - MAG COAT 70% START

11.8 ft. - General Observation - GREASE COAT ON MAG COAT FROM HOT SEWAGE

63.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

217.7 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE UNDER MAG COAT