Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 20, 2020, 11:04 AM
  • F 0209_F 0208_8202020_041916.mp4

Date
08/20/2020
W/O
0838782
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00048
PipeID
P10339
Time
4:04 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1541
Sewer Name
F JOINT OUTFALL F - UNIT 7F
City
CERRITOS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
38
Purpose
Capital Improvement Program Assesment
Project
20200818MDM_JOINT_OUTFALL_UNIT_7F
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Upstream MH
F 0209
Downstream MH
F 0208
Dir. of Survey
Downstream
Length Surveyed
500.7 ft.
Total Length
500.7 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
3225
O&M Rating
16
Overall Index
2
Overall Quick
Overall Rating
18
Pipe schematic from manhole F 0209 to F 0208
MH: F 0209MH: F 0208downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:15AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. MGO - General Observation - MAG COAT 70% START2 ft. MGO - General Observation - GREASE COAT ON MAG COAT FROM HOT SEWAGE2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT28.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 02 to 04 o'clock, , within 8 inches of joint: NO28.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Capped73.4 ft. MWL - Water Level, 5 %of cross sectional area75.9 ft. MGO - General Observation - GREASE COAT ON MAG COAT119.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Capped119.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 02 to 04 o'clock, , within 8 inches of joint: NO206.6 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Open-100% MINERIAL DEPOSIYE206.6 ft. DAE - Deposits Attached Encrustation, 20 %of cross sectional area, from 01 to 05 o'clock, , within 8 inches of joint: NO313.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Capped313.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Capped361 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6" - Active361 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 11 o'clock, , within 8 inches of joint: NO397.9 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 01 to 05 o'clock, , within 8 inches of joint: NO397.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Capped488.4 ft. DAE - Deposits Attached Encrustation, 20 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES500.2 ft. MGO - General Observation - GREASE COAT ON MAG COAT FINISH500.2 ft. MGO - General Observation - 70% MAG COAT FINISH500.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE UNDER MAG COAT500.7 ft. AMH - Downstream Manhole, Survey Ends - 5:00AM

Observation photos (11)

  • General Observation - MAG COAT 70% START

    2 ft. - General Observation - MAG COAT 70% START

  • General Observation - GREASE COAT ON MAG COAT FROM HOT SEWAGE

    2 ft. - General Observation - GREASE COAT ON MAG COAT FROM HOT SEWAGE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 02 to 04 o'clock,  , within 8 inches of joint: NO

    28.1 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 02 to 04 o'clock, , within 8 inches of joint: NO

  • General Observation - GREASE COAT ON MAG COAT

    75.9 ft. - General Observation - GREASE COAT ON MAG COAT

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Open-100% MINERIAL DEPOSIYE

    206.6 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Open-100% MINERIAL DEPOSIYE

  • Deposits Attached Encrustation, 20 %of cross sectional area, from 01 to 05 o'clock,  , within 8 inches of joint: NO

    206.6 ft. - Deposits Attached Encrustation, 20 %of cross sectional area, from 01 to 05 o'clock, , within 8 inches of joint: NO

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 11 o'clock,  , within 8 inches of joint: NO

    361 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 11 o'clock, , within 8 inches of joint: NO

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 01 to 05 o'clock,  , within 8 inches of joint: NO

    397.9 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 01 to 05 o'clock, , within 8 inches of joint: NO

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Capped

    397.9 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Capped

  • Deposits Attached Encrustation, 20 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    488.4 ft. - Deposits Attached Encrustation, 20 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

Observations (25)

DistanceCodeObservation
361TFActive
500.7AMH5:00AM
500.2MGOGREASE COAT ON MAG COAT FINISH
500.2MGO70% MAG COAT FINISH
397.9DAE
73.4MWL
313.9TFCCapped
2MGOMAG COAT 70% START
75.9MGOGREASE COAT ON MAG COAT
28.1DAE
28.1TFCCapped
361DAE
397.9TFCCapped
206.6TFDOpen-100% MINERIAL DEPOSIYE
0AMH4:15AM
0MWM
2MGOGREASE COAT ON MAG COAT FROM HOT SEWAGE
2SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
119.7TFCCapped
313.9TFCCapped
206.6DAE
119.7DAE
0MWL
500.2SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
488.4DAE

Properties (6)

custom_field_three
BLISTERING PEELING CONCRETE
custom_field_two
3
customer
LACSD
datetime
2020-08-20T04:04:02-07:00
documentation
MARTIN,OLIVER 111,BARR,CASTILLO
is_lateral_inspection
false