Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 24, 2020, 11:15 AM
  • F 0030_F 0029_8242020_042729.mp4

Date
08/24/2020
W/O
0838961
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00033
PipeID
P10120
Time
4:15 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1544
Sewer Name
F JOINT OUTFALL F - UNIT 1
City
PARAMOUNT
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20200824MDM_JOINT_OUTFALL_F_UNIT_1
Material
Reinforced Concrete Pipe
Shape
Circular
Height
69 in.
Upstream MH
F 0030
Downstream MH
F 0029
Dir. of Survey
Downstream
Length Surveyed
520.3 ft.
Total Length
520.3 ft.
Structural Index
5
Structural Quick
5542
Structural Rating
33
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
37
Pipe schematic from manhole F 0030 to F 0029
MH: F 0030MH: F 0029downstream0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:15AM2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. MGO - General Observation - 50% MAG COAT START2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR CORRODED & BROKEN39.8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN CIRCUM REBAR69.3 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG111.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR111.2 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6" - Active343.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR476.4 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG & CIRCUM REBAR520.3 ft. MGO - General Observation - 50% MAG COAT FINISH520.3 ft. AMH - Downstream Manhole, Survey Ends - 4:50AM520.3 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG520.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR CORRODED & BROKEN

Observation photos (8)

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - 50% MAG COAT START

    2 ft. - General Observation - 50% MAG COAT START

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR CORRODED & BROKEN

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR CORRODED & BROKEN

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN CIRCUM REBAR

    39.8 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN CIRCUM REBAR

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    69.3 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    111.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    343.3 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG & CIRCUM REBAR

    476.4 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG & CIRCUM REBAR

Observations (16)

DistanceCodeObservation
343.3SRCCIRCUM REBAR
2SAMSEVERE AGG
0MWL
520.3MGO50% MAG COAT FINISH
520.3AMH4:50AM
111.2SRCCIRCUM REBAR
520.3SAMSEVERE AGG
476.4SRCLONG & CIRCUM REBAR
0MWM
2MGO50% MAG COAT START
39.8SRCBROKEN CIRCUM REBAR
69.3SAMSEVERE AGG
111.2TFActive
2SRCLONG & CIRCUM REBAR CORRODED & BROKEN
520.3SRCLONG & CIRCUM REBAR CORRODED & BROKEN
0AMH4:15AM

Properties (6)

custom_field_three
LONG & CIRCUM REBAR CORRODED & BROKEN
custom_field_two
1
customer
LACSD
datetime
2020-08-24T04:15:59-07:00
documentation
MARTIN,OLIVER 111,BARR,CASTILLO
is_lateral_inspection
false