Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 24, 2020, 09:46 AM
  • F 0031_F 0030_8242020_025501.mp4

Date
08/24/2020
W/O
0838961
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00033
PipeID
P10121
Time
2:46 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1544
Sewer Name
F JOINT OUTFALL F - UNIT 1
City
PARAMOUNT
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20200824MDM_JOINT_OUTFALL_F_UNIT_1
Material
Reinforced Concrete Pipe
Shape
Circular
Height
69 in.
Upstream MH
F 0031
Downstream MH
F 0030
Dir. of Survey
Downstream
Length Surveyed
337.8 ft.
Total Length
337.8 ft.
Structural Index
5
Structural Quick
5541
Structural Rating
29
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
33
Pipe schematic from manhole F 0031 to F 0030
MH: F 0031MH: F 0030downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:50AM0 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. MWL - Water Level, 50 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. MGO - General Observation - MAG COAT 50% START2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR CORRODED & MISSING3.7 ft. MGP - General Photograph - LONG REBAR CORRODED MISSING18.8 ft. SRC - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - BROKEN REBAR45.1 ft. SRC - Surface Reinforcement Corroded, from 09 to 01 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND REBAR99 ft. SRC - Surface Reinforcement Corroded, from 09 to 01 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR99 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6" - Open174.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Active211.2 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6" - Active293.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR337 ft. MGO - General Observation - 50% MAG COAT FINISH337 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG337 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - LONG &CIRCUM REBAR CORRODED & MISSING337.8 ft. AMH - Downstream Manhole, Survey Ends - 3:20AM

Observation photos (8)

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - MAG COAT 50% START

    2 ft. - General Observation - MAG COAT 50% START

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR CORRODED & MISSING

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR CORRODED & MISSING

  • General Photograph - LONG REBAR CORRODED MISSING

    3.7 ft. - General Photograph - LONG REBAR CORRODED MISSING

  • Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    18.8 ft. - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • Surface Reinforcement Corroded, from 09 to 01 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND REBAR

    45.1 ft. - Surface Reinforcement Corroded, from 09 to 01 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND REBAR

  • Surface Reinforcement Corroded, from 09 to 01 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

    99 ft. - Surface Reinforcement Corroded, from 09 to 01 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

    293.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

Observations (18)

DistanceCodeObservation
211.2TFActive
18.8SRCBROKEN REBAR
337.8AMH3:20AM
3.7MGPLONG REBAR CORRODED MISSING
0AMH2:50AM
2SAMSEVERE AGG
337MGO50% MAG COAT FINISH
0MWM
293.2SRCLONG CIRCUM REBAR
337SAMSEVERE AGG
45.1SRCCORRISON BEYOUND REBAR
99SRCLONG CIRCUM REBAR
174.6TFActive
0MWL
2MGOMAG COAT 50% START
2SRCLONG & CIRCUM REBAR CORRODED & MISSING
337SRCLONG &CIRCUM REBAR CORRODED & MISSING
99TFOpen

Properties (6)

custom_field_three
LONG & CIRCUM REBAR CORRODED & MISSING
custom_field_two
1
customer
LACSD
datetime
2020-08-24T02:46:02-07:00
documentation
MARTIN,OLIVER 111,BARR,CASTILLO
is_lateral_inspection
false