Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 17, 2020, 04:34 AM
  • F 0078_F 0077_06162020_232154.mp4

Date
06/16/2020
W/O
833709
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00043
PipeID
P10282
Time
9:34 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7732
Sewer Name
JOINT OUTFALL F - UNIT 7A
City
CERRITOS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
Routine Assessment
Project
RFIR_WO_833709_TV02203_JUN2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Width
33 in.
Upstream MH
F 0078
Downstream MH
F 0077
Dir. of Survey
Downstream
Length Surveyed
536.2 ft.
Total Length
536.2 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole F 0078 to F 0077
MH: F 0078MH: F 0077downstream0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - F 00782.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start535.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish535.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish535.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish536.2 ft. AMH - Downstream Manhole, Survey Ends - F 0077 ZOOMED IN

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
2.1SAP
0MWM
536.2AMHF 0077 ZOOMED IN
2.1SRV
535.2SSS
535.2SAP
535.2SRV
2.1SSS
0MWL
0AMHF 0078

Properties (7)

additional_info
SC411390
custom_field_three
SURFACE REINFORCEMENT VISIBLE, AGG., SPALL..
custom_field_two
2
customer
1
datetime
2020-06-16T21:34:46-07:00
documentation
PROPIPE
is_lateral_inspection
false