Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 17, 2020, 05:30 AM
  • H 0127_H 0126_06162020_224420.mp4

Date
06/16/2020
W/O
833497
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00166
PipeID
P10579
Time
10:30 PM
Certificate
U-111-11880
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7698
Sewer Name
JOINT OUTFALL H - UNIT 1G
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Routine Assessment
Project
WO_833497_TV01098_JUN2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
H 0127
Downstream MH
H 0126
Dir. of Survey
Downstream
Length Surveyed
414.1 ft.
Total Length
414.1 ft.
Structural Index
3
Structural Quick
3O2O
Structural Rating
400
O&M Index
2
O&M Quick
2O00
O&M Rating
164
Overall Index
2
Overall Quick
Overall Rating
564
Pipe schematic from manhole H 0127 to H 0126
MH: H 0127MH: H 0126downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - H 01270 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start8.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start411.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish411.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish411.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish414.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE414.1 ft. AMH - Downstream Manhole, Survey Ends - H 0126

Observation photos (5)

  • General Observation - CONNECTION AT MH 9 O'CLOCK

    0 ft. - General Observation - CONNECTION AT MH 9 O'CLOCK

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    414.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (13)

DistanceCodeObservation
0MGOCOCKROACHES IN MANHOLE
414.1MGOCOCKROACHES IN MANHOLE
0MWM
8.9SSS
0MGOCONNECTION AT MH 9 O'CLOCK
2DAGS
411.3SAP
0AMHH 0127
411.3DAGS
8.9SAP
411.3SSS
414.1AMHH 0126
0MWL

Properties (6)

additional_info
SC411290
custom_field_two
3
customer
1
datetime
2020-06-16T22:30:12-07:00
documentation
PRO PIPE
is_lateral_inspection
false