Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 17, 2020, 05:44 AM
  • H 0126_H 0125_06162020_230252.mp4

Date
06/16/2020
W/O
833497
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00166
PipeID
P10578
Time
10:44 PM
Certificate
U-111-11880
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7698
Sewer Name
JOINT OUTFALL H - UNIT 1G
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Routine Assessment
Project
WO_833497_TV01098_JUN2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
H 0126
Downstream MH
H 0125
Dir. of Survey
Downstream
Length Surveyed
409.2 ft.
Total Length
409.2 ft.
Structural Index
3
Structural Quick
3O2O
Structural Rating
405
O&M Index
2
O&M Quick
2O00
O&M Rating
164
Overall Index
2
Overall Quick
Overall Rating
569
Pipe schematic from manhole H 0126 to H 0125
MH: H 0126MH: H 0125downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 01262 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start242 ft. TBI - Tap Break-In Intruding, at 10 o'clock, -, #v, within 8 inches of joint: NO, 8", 2", 8"406.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish406.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish406.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish409.2 ft. AMH - Downstream Manhole, Survey Ends - H 0125409.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Intruding, at 10 o'clock, -, #v, within 8 inches of joint: NO, 8", 2", 8"

    242 ft. - Tap Break-In Intruding, at 10 o'clock, -, #v, within 8 inches of joint: NO, 8", 2", 8"

  • General Observation - COCKROACHES IN MANHOLE

    409.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (13)

DistanceCodeObservation
2DAGS
409.2AMHH 0125
2SSS
0MGOCOCKROACHES IN MANHOLE
0MWM
0MWL
409.2MGOCOCKROACHES IN MANHOLE
406.3SSS
0AMHH 0126
406.3DAGS
406.3SAP
2SAP
242TBI

Properties (6)

additional_info
SC411290
custom_field_two
3
customer
1
datetime
2020-06-16T22:44:53-07:00
documentation
PRO PIPE
is_lateral_inspection
false