Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 16, 2020, 05:07 AM
  • J 0005_J 0004_07152020_223414.mp4

Date
07/15/2020
W/O
839187
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00060
PipeID
P11593
Time
10:07 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7920
Sewer Name
JOINT OUTFALL J - UNIT 2A
City
HARBOR CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_839187_TV08171_JUL2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
57 in.
Upstream MH
J 0005
Downstream MH
J 0004
Dir. of Survey
Downstream
Length Surveyed
640.1 ft.
Total Length
640.1 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole J 0005 to J 0004
MH: J 0005MH: J 0004downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 00050 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0.1 ft. MWM - Water Mark, 25 %of cross sectional area2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start580.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"639.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish640.1 ft. AMH - Downstream Manhole, Survey Ends - J 0004640.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish640.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK640.1 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0MWL
640.1AMHJ 0004
2.1SSS
2.1SAP
639.3SSS
640.1SAP
640.1MGOCONNECTION AT MH 3 O'CLOCK
580.1TFA
0AMHJ 0005
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0.1MWM
640.1MGOCONNECTION AT MH 9 O'CLOCK

Properties (7)

additional_info
SC411779
custom_field_three
SURFACE AGGREGATE PROJECTING/SPALLING
custom_field_two
2
customer
1
datetime
2020-07-15T22:07:37-07:00
documentation
PROPIPE
is_lateral_inspection
false