Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 16, 2020, 06:00 AM
  • J 0001_D 0150_07152020_231059.mp4

Date
07/15/2020
W/O
839187
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00060
PipeID
P11588
Time
11:00 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7920
Sewer Name
JOINT OUTFALL J - UNIT 2A
City
HARBOR CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_839187_TV08171_JUL2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
57 in.
Upstream MH
J 0001
Downstream MH
D 0150
Dir. of Survey
Downstream
Length Surveyed
211.6 ft.
Total Length
211.6 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole J 0001 to D 0150
MH: J 0001MH: D 0150downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 00012.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start152.4 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start211 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish211.6 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK211.6 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish211.6 ft. AMH - Downstream Manhole, Survey Ends - D 0150211.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    152.4 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0MWL
211.6MGOACTIVE CONNECTION AT MH 9 O'CLOCK
152.4SRV
0MWM
2.1SAP
211SAP
2.1SSS
211.6SRV
0AMHJ 0001
211.6AMHD 0150
211.6SSS

Properties (7)

additional_info
SC411779
custom_field_three
AGGREGATE PROJECTING/ REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2020-07-15T23:00:57-07:00
documentation
PROPIPE
is_lateral_inspection
false