Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 17, 2020, 04:01 AM
  • H 0375_H 0342_07162020_214756.mp4

Date
07/16/2020
W/O
839012
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00177
PipeID
P10804
Time
9:01 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7923
Sewer Name
JOINT OUTFALL H - UNIT 5A
City
PICO RIVERA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_839012_TV15225_JUL2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
66 in.
Width
66 in.
Upstream MH
H 0375
Downstream MH
H 0342
Dir. of Survey
Downstream
Length Surveyed
968 ft.
Total Length
968 ft.
Structural Index
4
Structural Quick
5132
Structural Rating
11
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
11
Pipe schematic from manhole H 0375 to H 0342
MH: H 0375MH: H 0342downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 03752.1 ft. MGO - General Observation - MAG COAT2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start924.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE967.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish967.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES968 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES968 ft. AMH - Downstream Manhole, Survey Ends - H 0342

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

    967.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES

    968 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (10)

DistanceCodeObservation
2.1MGOMAG COAT
967.9SAV
968SRV
968AMHH 0342
2.1SAV
0MWL
924.3TFACTIVE
0MWM
0AMHH 0375
967.9SAP

Properties (8)

additional_info
SC411782
custom_field_three
AGGREGATE VISIBLE/ AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2020-07-16T21:01:04-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
38626