Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 17, 2020, 04:37 AM
  • 02 1171_02 1170_07162020_221749.mp4

Date
07/16/2020
W/O
839003
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00350
PipeID
P04565
Time
9:37 PM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7327
Sewer Name
GARFIELD AVENUE TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_839003_TV02336_JUL2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
24 in.
Upstream MH
02 1170
Downstream MH
02 1171
Dir. of Survey
Upstream
Length Surveyed
297.6 ft.
Total Length
297.6 ft.
Structural Index
4
Structural Quick
4400
Structural Rating
16
O&M Index
2
O&M Quick
512K
O&M Rating
121
Overall Index
2
Overall Quick
Overall Rating
137
Pipe schematic from manhole 02 1170 to 02 1171
MH: 02 1170MH: 02 1171upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 11713.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Finish15.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"66 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"73.7 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES115.7 ft. FM - Fracture Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES116.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"167.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"214.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES218.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"266.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"290.8 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES290.8 ft. MGO - General Observation - VOID PRESENT @ 2 O'CLOCK - WITHIN 8" OF JOINT295.6 ft. MGO - General Observation - 5% JOINT OFFSET THROUGHOUT LINE295.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start297.6 ft. AMH - Downstream Manhole, Survey Begins - 02 1170297.6 ft. MWL - Water Level, 5 %of cross sectional area297.6 ft. MWM - Water Mark, 85 %of cross sectional area

Observation photos (4)

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    6.8 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    83 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

    181.9 ft. - Fracture Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    223.9 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
79.2TFC
130.3TFC
2MGO5% JOINT OFFSET THROUGHOUT LINE
0AMH02 1170
297.6AMH02 1171
2DAGS
282.4TFC
181.9FM
83FM
181TFC
294.3DAGS
0MWL
223.9FM
6.8FM
31.4TF
231.6TFC
0MWM
6.8MGOVOID PRESENT @ 2 O'CLOCK - WITHIN 8" OF JOINT

Properties (7)

additional_info
SC411320
custom_field_three
multiple fracture
custom_field_two
1
customer
1
datetime
2020-07-16T21:37:20-07:00
documentation
PRO PIPE
is_lateral_inspection
false