Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 28, 2020, 07:14 AM
  • H 0869_H 0489A_07282020_003222.mp4

Date
07/28/2020
W/O
839001
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00181
PipeID
P20460
Time
12:14 AM
Certificate
U-111-11880
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7885
Sewer Name
JOINT OUTFALL H - UNIT 6
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
RFIR_WO_839001_TV15212_JUL2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
H 0869
Downstream MH
H 0489A
Dir. of Survey
Downstream
Length Surveyed
356.6 ft.
Total Length
356.6 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
210
O&M Index
2
O&M Quick
2M00
O&M Rating
140
Overall Index
3
Overall Quick
Overall Rating
350
Pipe schematic from manhole H 0869 to H 0489A
MH: H 0869MH: H 0489Adownstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 08690 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - STOP LOG CONNECTION IN MH, 3 O' CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COAT THROUGHOUT LINE24.5 ft. MGO - General Observation - SURFACE REINFORCEMENT VISIBLE @ 10 O'CLOCK79.3 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"354 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish354 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish356.6 ft. AMH - Downstream Manhole, Survey Ends - H 0489A

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0MWM
0AMHH 0869
2DAGS
0MWL
354DAGS
24.5MGOSURFACE REINFORCEMENT VISIBLE @ 10 O'CLOCK
354SAP
79.3TBA
2SAP
2MGOMAG COAT THROUGHOUT LINE
0MGOSTOP LOG CONNECTION IN MH, 3 O' CLOCK
356.6AMHH 0489A

Properties (7)

additional_info
SC411725
custom_field_three
PROJECTING AGGREGATE, SURFC. REINFORCEMNT. VISIBL.
custom_field_two
2
customer
1
datetime
2020-07-28T00:14:17-07:00
documentation
PRO PIPE
is_lateral_inspection
false