Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 2, 2020, 08:27 AM
  • 32 1134_32 1133 _07022020_013901.mp4

Date
07/02/2020
W/O
838954
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00842
PipeID
P19585
Time
1:27 AM
Certificate
U-111-11880
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7864
Sewer Name
SOLEDAD CANYON TRUNK, SECTION 5
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
11
Purpose
Routine Assessment
Project
WO_838954_TV32029_JUL2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
32 1134
Downstream MH
32 1133
Dir. of Survey
Downstream
Length Surveyed
98.9 ft.
Total Length
98.9 ft.
Structural Index
4
Structural Quick
4231
Structural Rating
11
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
17
Pipe schematic from manhole 32 1134 to 32 1133
MH: 32 1134MH: 32 1133downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 11340 ft. MWL - Water Level, 25 %of cross sectional area2 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start50.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start94.5 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES94.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish98 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish98.9 ft. AMH - Downstream Manhole, Survey Ends - 32 1133

Observation photos (4)

  • Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    2 ft. - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    50.1 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    94.5 ft. - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

Observations (10)

DistanceCodeObservation
98DAGS
0MWM
2FM
94.5FM
0AMH32 1134
0MWL
50.1CM
2DAGS
98.9AMH32 1133
94.5CM

Properties (7)

additional_info
SC411703
custom_field_three
MULTIPLE CRACKS/MULTIPLE FRACTURES
custom_field_two
3
customer
1
datetime
2020-07-02T01:27:27-07:00
documentation
PRO PIPE
is_lateral_inspection
false