Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 29, 2020, 08:51 AM
  • 18 0892_18 0891 _06292020_021543.mp4

Date
06/29/2020
W/O
833718
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00709
PipeID
P14743
Time
1:51 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7810
Sewer Name
SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
26
Purpose
Routine Assessment
Project
WO_833718_TV18101_JUN2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
18 0892
Downstream MH
18 0891
Dir. of Survey
Downstream
Length Surveyed
627.6 ft.
Total Length
627.6 ft.
Structural Index
2
Structural Quick
2X00
Structural Rating
248
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
248
Pipe schematic from manhole 18 0892 to 18 0891
MH: 18 0892MH: 18 0891downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 08920 ft. MWL - Water Level, 15 %of cross sectional area6.4 ft. MGO - General Observation - MAG COATING ATTATCHED6.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start625.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish627.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0891

Observation photos (1)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
0MWM
625.7SSS
0AMH18 0892
0MWL
6.4MGOMAG COATING ATTATCHED
627.6AMH18 0891
6.4SSS

Properties (7)

additional_info
SC411620
custom_field_three
SURFACE SPALLING
custom_field_two
3
customer
1
datetime
2020-06-29T01:51:10-07:00
documentation
PROPIPE
is_lateral_inspection
false