Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 25, 2020, 05:20 AM
  • 18 0847_18 0846 _06242020_231011.mp4

Date
06/24/2020
W/O
833718
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00709
PipeID
P14702
Time
10:20 PM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7809
Sewer Name
SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37A
Purpose
Routine Assessment
Project
WO_833718_TV18101_JUN2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
18 0847
Downstream MH
18 0846
Dir. of Survey
Downstream
Length Surveyed
977.7 ft.
Total Length
977.7 ft.
Structural Index
3
Structural Quick
5f3f
Structural Rating
1908
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
1912
Pipe schematic from manhole 18 0847 to 18 0846
MH: 18 0847MH: 18 0846downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 084712.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start12.4 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start66.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start976.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish976.6 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish976.8 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish977.6 ft. MGO - General Observation - CONNECTION IN MH, 3 O' CLOCK977.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0846

Observation photos (3)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    12.4 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    12.4 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    66.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
66.3SSS
977.7AMH18 0846
0MWM
976.8SAP
0MWL
977.6MGOCONNECTION IN MH, 3 O' CLOCK
976.2SSS
976.6SRV
12.4SAP
0AMH18 0847
12.4SRV

Properties (7)

additional_info
SC411619
custom_field_three
AGGREGATE PROJECTING, REINFORCEMEN VISIBLE
custom_field_two
2
customer
1
datetime
2020-06-24T22:20:31-07:00
documentation
PROPIPE
is_lateral_inspection
false