- Date
- 07/01/2020
- W/O
- 833718
- Weather
- Dry
- Operator/Surveyor
- J. BUENROSTRO
- Sewer ID
- Z00709
- PipeID
- P14567
- Time
- 2:45 AM
- Certificate
- U-715-07000770
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K7812
- Sewer Name
- SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
- City
- NORWALK
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 31
- Purpose
- Routine Assessment
- Project
- WO_833718_TV18101_JUN2020
- Sewer Type
- Siphon
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 54 in.
- Width
- 54 in.
- Upstream MH
- 18 0716
- Downstream MH
- 18 0715
- Dir. of Survey
- Downstream
- Length Surveyed
- 2.4 ft.
- Total Length
- 2.4 ft.
- Structural Index
- 4
- Structural Quick
- 5131
- Structural Rating
- 8
- O&M Index
- 4
- O&M Quick
- 5121
- O&M Rating
- 7
- Overall Index
- 4
- Overall Quick
- —
- Overall Rating
- 15
Pipe schematic from manhole 18 0716 to 18 0715 Observation photos (3)

2.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES

2.4 ft. - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES

2.4 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES