Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 1, 2020, 07:50 AM
  • 15 0674_15 0673_07012020_010023.mp4

Date
07/01/2020
W/O
833764
Weather
Dry
Operator/Surveyor
EN. RUIZ
Sewer ID
Z00602
PipeID
P12566
Time
12:50 AM
Certificate
U-116-07001919
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7770
Sewer Name
EL MONTE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
WO_833764_TV15005_JUN2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0674
Downstream MH
15 0673
Dir. of Survey
Downstream
Length Surveyed
146.9 ft.
Total Length
146.9 ft.
Structural Index
3
Structural Quick
3E2D
Structural Rating
130
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
130
Pipe schematic from manhole 15 0674 to 15 0673
MH: 15 0674MH: 15 0673downstream0 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 06742.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start28.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start143.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish143.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish146.8 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK146.9 ft. AMH - Downstream Manhole, Survey Ends - 15 0673146.9 ft. MGO - General Observation - COCKROACHES IN MH

Observation photos (4)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    28.1 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

  • General Observation - COCKROACHES IN MH

    146.9 ft. - General Observation - COCKROACHES IN MH

Observations (12)

DistanceCodeObservation
143.9SSS
28.1SSS
146.9AMH15 0673
143.9SAP
0MGOCONNECTION AT MH, 3 O'CLOCK
0MWM
146.9MGOCOCKROACHES IN MH
0MGOCOCKROACHES IN MH
0MWL
146.8MGOCONNECTION AT MH, 9 O'CLOCK
2.1SAP
0AMH15 0674

Properties (7)

additional_info
SC427455
custom_field_three
SURFACE AGGREGATE, SPALLING
custom_field_two
3
customer
1
datetime
2020-07-01T00:50:58-07:00
documentation
PRO PIPE
is_lateral_inspection
false