Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 18, 2020, 06:10 AM
  • 15 0670_15 0669_06172020_232113.mp4

Date
06/17/2020
W/O
833764
Weather
Dry
Operator/Surveyor
EN. RUIZ
Sewer ID
Z00602
PipeID
P12562
Time
11:10 PM
Certificate
U-116-07001919
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7766
Sewer Name
EL MONTE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
WO_833764_TV15005_JUN2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0670
Downstream MH
15 0669
Dir. of Survey
Downstream
Length Surveyed
112.7 ft.
Total Length
112.7 ft.
Structural Index
3
Structural Quick
3C2C
Structural Rating
106
O&M Index
2
O&M Quick
2C00
O&M Rating
44
Overall Index
2
Overall Quick
Overall Rating
150
Pipe schematic from manhole 15 0670 to 15 0669
MH: 15 0670MH: 15 0669downstream0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 06702.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start11.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start33.8 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"93.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 8"106.1 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"110.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish110.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish110.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish112.7 ft. MGO - General Observation - COCKROACHES IN MH112.7 ft. AMH - Downstream Manhole, Survey Ends - 15 0669

Observation photos (8)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • General Observation - CONNECTION AT MH, 3 O'CLOCK

    0 ft. - General Observation - CONNECTION AT MH, 3 O'CLOCK

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    2.1 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    11.1 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

  • Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"

    33.8 ft. - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 8"

    93.4 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"

    106.1 ft. - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"

Observations (16)

DistanceCodeObservation
112.7MGOCOCKROACHES IN MH
110.2SSS
112.7AMH15 0669
0MGOCOCKROACHES IN MH
93.4TB
2.1SAV
110.2DAGS
106.1TF
0MGOCONNECTION AT MH, 3 O'CLOCK
0MWM
33.8TFC
0MWL
110.2SAV
2.1DAGS
0AMH15 0670
11.1SSS

Properties (7)

additional_info
SC411478
custom_field_three
AGGREGATE, GREASE, SPALLING
custom_field_two
3
customer
1
datetime
2020-06-17T23:10:03-07:00
documentation
PRO PIPE
is_lateral_inspection
false