Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 18, 2020, 06:43 AM
  • 15 0668_15 0667_06172020_235216.mp4

Date
06/17/2020
W/O
833764
Weather
Dry
Operator/Surveyor
EN. RUIZ
Sewer ID
Z00602
PipeID
P12560
Time
11:43 PM
Certificate
U-116-07001919
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7766
Sewer Name
EL MONTE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
WO_833764_TV15005_JUN2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0668
Downstream MH
15 0667
Dir. of Survey
Downstream
Length Surveyed
114.2 ft.
Total Length
114.2 ft.
Structural Index
3
Structural Quick
3C2C
Structural Rating
110
O&M Index
2
O&M Quick
2C00
O&M Rating
44
Overall Index
2
Overall Quick
Overall Rating
154
Pipe schematic from manhole 15 0668 to 15 0667
MH: 15 0668MH: 15 0667downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 06680 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK0 ft. MWM - Water Mark, 20 %of cross sectional area2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start2.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start2.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start23.5 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"32.9 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"102.1 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"111.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish111.9 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish111.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish114.2 ft. AMH - Downstream Manhole, Survey Ends - 15 0667114.2 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK114.2 ft. MGO - General Observation - COCKROACHES IN MH

Observation photos (7)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • General Observation - CONNECTION AT MH, 3 O'CLOCK

    0 ft. - General Observation - CONNECTION AT MH, 3 O'CLOCK

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    2.2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    2.2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

  • General Observation - CONNECTION AT MH, 9 O'CLOCK

    114.2 ft. - General Observation - CONNECTION AT MH, 9 O'CLOCK

  • General Observation - COCKROACHES IN MH

    114.2 ft. - General Observation - COCKROACHES IN MH

Observations (17)

DistanceCodeObservation
114.2AMH15 0667
114.2MGOCONNECTION AT MH, 9 O'CLOCK
2.2SSS
2.2SAV
0AMH15 0668
0MGOCOCKROACHES IN MH
2.1DAGS
111.9DAGS
23.5TF
0MWL
114.2MGOCOCKROACHES IN MH
102.1TF
32.9TFC
111.9SAV
0MGOCONNECTION AT MH, 3 O'CLOCK
111.9SSS
0MWM

Properties (7)

additional_info
SC411478
custom_field_three
AGGREGATE, SPALLING, GREASE
custom_field_two
3
customer
1
datetime
2020-06-17T23:43:22-07:00
documentation
PRO PIPE
is_lateral_inspection
false