Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 18, 2020, 06:55 AM
  • 15 0667_15 0666_06182020_000936.mp4

Date
06/17/2020
W/O
833764
Weather
Dry
Operator/Surveyor
EN. RUIZ
Sewer ID
Z00602
PipeID
P12559
Time
11:55 PM
Certificate
U-116-07001919
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7766
Sewer Name
EL MONTE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
WO_833764_TV15005_JUN2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0667
Downstream MH
15 0666
Dir. of Survey
Downstream
Length Surveyed
297.4 ft.
Total Length
297.4 ft.
Structural Index
3
Structural Quick
413K
Structural Rating
299
O&M Index
2
O&M Quick
2K00
O&M Rating
118
Overall Index
2
Overall Quick
Overall Rating
417
Pipe schematic from manhole 15 0667 to 15 0666
MH: 15 0667MH: 15 0666downstream0 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. AMH - Upstream Manhole, Survey Begins - 15 06672.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start2.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start2.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start39.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"69.8 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"93.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"126.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"184 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"196.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"198.2 ft. FM - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES295 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish295 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish295 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish297.4 ft. MGO - General Observation - COCKROACHES IN MH297.4 ft. AMH - Downstream Manhole, Survey Ends - 15 0666297.4 ft. MGO - General Observation - CONNECTION AT MH, 3 AND 9 O'CLOCK

Observation photos (8)

  • General Observation - CONNECTION AT MH, 9 O'CLOCK

    0 ft. - General Observation - CONNECTION AT MH, 9 O'CLOCK

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    2.2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    2.2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

  • Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    198.2 ft. - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MH

    297.4 ft. - General Observation - COCKROACHES IN MH

  • General Observation - CONNECTION AT MH, 3 AND 9 O'CLOCK

    297.4 ft. - General Observation - CONNECTION AT MH, 3 AND 9 O'CLOCK

Observations (19)

DistanceCodeObservation
0MGOCONNECTION AT MH, 9 O'CLOCK
184TF
69.8TF
297.4MGOCOCKROACHES IN MH
2.1DAGS
39.2TFC
2.2SAV
295DAGS
0MGOCOCKROACHES IN MH
93.6TFC
126.9TB
2.2SSS
295SSS
297.4AMH15 0666
196.5TFC
297.4MGOCONNECTION AT MH, 3 AND 9 O'CLOCK
198.2FM
0AMH15 0667
295SAV

Properties (7)

additional_info
SC411478
custom_field_three
GREASE, SPALLING, AGGREGATE, FRACTURES
custom_field_two
3
customer
1
datetime
2020-06-17T23:55:02-07:00
documentation
PRO PIPE
is_lateral_inspection
false