Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 18, 2020, 07:43 AM
  • 15 0666_15 0665_06182020_012824.mp4

Date
06/18/2020
W/O
833764
Weather
Dry
Operator/Surveyor
EN. RUIZ
Sewer ID
Z00602
PipeID
P12558
Time
12:43 AM
Certificate
U-116-07001919
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7766
Sewer Name
EL MONTE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
WO_833764_TV15005_JUN2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0666
Downstream MH
15 0665
Dir. of Survey
Downstream
Length Surveyed
297 ft.
Total Length
297 ft.
Structural Index
3
Structural Quick
413K
Structural Rating
290
O&M Index
2
O&M Quick
412K
O&M Rating
120
Overall Index
2
Overall Quick
Overall Rating
410
Pipe schematic from manhole 15 0666 to 15 0665
MH: 15 0666MH: 15 0665downstream0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH, 3 AND 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 15 06662.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: NO, Start2.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start15.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start23 ft. FM - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES69.8 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"166.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"175.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"225.1 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"227.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"242.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"294.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: NO, Finish294.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish294.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish297 ft. MGO - General Observation - COCKROACHES IN MH297 ft. AMH - Downstream Manhole, Survey Ends - 15 0665

Observation photos (7)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • General Observation - CONNECTION AT MH, 3 AND 9 O'CLOCK

    0 ft. - General Observation - CONNECTION AT MH, 3 AND 9 O'CLOCK

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: NO, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: NO, Start

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    2.1 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    15.9 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

  • Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    23 ft. - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MH

    297 ft. - General Observation - COCKROACHES IN MH

Observations (20)

DistanceCodeObservation
0MGOCOCKROACHES IN MH
297MGOCOCKROACHES IN MH
294.3DAGS
175.9TF
294.3SSS
2.1DAGS
297AMH15 0665
225.1TB
15.9SSS
2.1SAV
0MWM
0MWL
166.7TF
242.6TF
0MGOCONNECTION AT MH, 3 AND 9 O'CLOCK
227.3TFC
69.8TF
294.3SAV
0AMH15 0666
23FM

Properties (7)

additional_info
SC411478
custom_field_three
AGGREGATE, SPALLING, GREASE, FRACTURES
custom_field_two
3
customer
1
datetime
2020-06-18T00:43:08-07:00
documentation
PRO PIPE
is_lateral_inspection
false