Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 1, 2020, 06:27 AM
  • 15 0660_B 0621_06302020_234238.mp4

Date
06/30/2020
W/O
833764
Weather
Dry
Operator/Surveyor
EN. RUIZ
Sewer ID
Z00602
PipeID
P12552
Time
11:27 PM
Certificate
U-116-07001919
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7770
Sewer Name
EL MONTE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
WO_833764_TV15005_JUN2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0660
Downstream MH
B 0621
Dir. of Survey
Downstream
Length Surveyed
416.3 ft.
Total Length
416.3 ft.
Structural Index
3
Structural Quick
3P2N
Structural Rating
403
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
403
Pipe schematic from manhole 15 0660 to B 0621
MH: 15 0660MH: B 0621downstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 15 06602.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start30.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start98 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"106.4 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"150.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"220 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"282.8 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"415.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish415.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish416.1 ft. MGO - General Observation - CONNECTION AT MH, 3 AND 9 O'CLOCK416.1 ft. MGO - General Observation - COCKROACHES IN MH416.3 ft. AMH - Downstream Manhole, Survey Ends - B 0621

Observation photos (4)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    30.2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

  • General Observation - COCKROACHES IN MH

    416.1 ft. - General Observation - COCKROACHES IN MH

Observations (17)

DistanceCodeObservation
2.1SAP
106.4TFC
98TF
416.1MGOCONNECTION AT MH, 3 AND 9 O'CLOCK
0MWL
415.7SAP
282.8TF
0MGOCOCKROACHES IN MH
416.3AMHB 0621
30.2SSS
0MWM
0MGOCONNECTION AT MH, 3 O'CLOCK
415.7SSS
150.4TF
416.1MGOCOCKROACHES IN MH
0AMH15 0660
220TB

Properties (7)

additional_info
SC427455
custom_field_three
SURFACE AGGREGATE, SPALLING
custom_field_two
3
customer
1
datetime
2020-06-30T23:27:16-07:00
documentation
PRO PIPE
is_lateral_inspection
false