Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 18, 2020, 05:23 AM
  • 01 0268_01 0267_06172020_223442.mp4

Date
06/17/2020
W/O
833688
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00218
PipeID
P01316
Time
10:23 PM
Certificate
U-111-11880
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7851
Sewer Name
SOUTH PARK AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_833688_TV01204_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
18 in.
Upstream MH
01 0268
Downstream MH
01 0267
Dir. of Survey
Downstream
Length Surveyed
332.2 ft.
Total Length
332.2 ft.
Structural Index
4
Structural Quick
4L00
Structural Rating
260
O&M Index
2
O&M Quick
412L
O&M Rating
136
Overall Index
3
Overall Quick
Overall Rating
396
Pipe schematic from manhole 01 0268 to 01 0267
MH: 01 0268MH: 01 0267downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 02680 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK, ACTIVE0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start5 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start85.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"105.5 ft. MWL - Water Level, 25 %of cross sectional area116 ft. MWM - Water Mark, 40 %of cross sectional area149.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"179.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"209.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"241.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"272.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"330.7 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish330.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish332.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK, ACTIVE332.2 ft. AMH - Downstream Manhole, Survey Ends - 01 0267332.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE332.2 ft. MGO - General Observation - CONNECTION AT MH, 9 OCLOCK, CAPPED

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    5 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    332.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (21)

DistanceCodeObservation
105.5MWL
179.1TFA
5FM
149.3TFA
332.2MGOCONNECTION AT MH 3 O'CLOCK, ACTIVE
0AMH01 0268
209.3TF
116MWM
330.7FM
2DAGS
332.2AMH01 0267
0MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK, ACTIVE
332.2MGOCOCKROACHES IN MANHOLE
0MWL
0MWM
272.2TFC
0MGOCOCKROACHES IN MANHOLE
85.2TFC
330.7DAGS
241.9TFC
332.2MGOCONNECTION AT MH, 9 OCLOCK, CAPPED

Properties (7)

additional_info
SC411292
custom_field_three
MULIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2020-06-17T22:23:00-07:00
documentation
PRO PIPE
is_lateral_inspection
false