Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 18, 2020, 05:57 AM
  • 01 0266A_01 0266_06172020_230445.mp4

Date
06/17/2020
W/O
833688
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00218
PipeID
P01313
Time
10:57 PM
Certificate
U-111-11880
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7851
Sewer Name
SOUTH PARK AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_833688_TV01204_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
18 in.
Upstream MH
01 0266A
Downstream MH
01 0266
Dir. of Survey
Downstream
Length Surveyed
118.8 ft.
Total Length
118.8 ft.
Structural Index
4
Structural Quick
4D00
Structural Rating
92
O&M Index
2
O&M Quick
412D
O&M Rating
50
Overall Index
3
Overall Quick
Overall Rating
142
Pipe schematic from manhole 01 0266A to 01 0266
MH: 01 0266AMH: 01 0266downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 01 0266A2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start3.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start28.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"62.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"117.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish117.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish118.8 ft. AMH - Downstream Manhole, Survey Ends - 01 0266118.8 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK118.8 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    118.8 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (14)

DistanceCodeObservation
117.8FM
117.8DAGS
2DAGS
0MWL
118.8AMH01 0266
118.8MGOCONNECTION AT MH 3 O'CLOCK
118.8MGOCOCKROACHES IN MANHOLE
0MWM
0MGOCONNECTION AT MH 9 O'CLOCK
28.3TFA
62.5TFC
3.1FM
0MGOCOCKROACHES IN MANHOLE
0AMH01 0266A

Properties (7)

additional_info
SC411292
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2020-06-17T22:57:50-07:00
documentation
PRO PIPE
is_lateral_inspection
false