Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 17, 2020, 09:18 AM
  • 01 0258_01 0257_06172020_022945.mp4

Date
06/17/2020
W/O
833688
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00218
PipeID
P01304
Time
2:18 AM
Certificate
U-111-11880
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7699
Sewer Name
SOUTH PARK AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_833688_TV01204_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
21 in.
Upstream MH
01 0258
Downstream MH
01 0257
Dir. of Survey
Downstream
Length Surveyed
285 ft.
Total Length
285 ft.
Structural Index
4
Structural Quick
4J00
Structural Rating
224
O&M Index
2
O&M Quick
412J
O&M Rating
116
Overall Index
3
Overall Quick
Overall Rating
340
Pipe schematic from manhole 01 0258 to 01 0257
MH: 01 0258MH: 01 0257downstream0 ft. MWM - Water Mark, 70 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 01 02580 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start3.5 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start147.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"185.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"225.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6"267.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"283.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Finish283.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish285 ft. MGO - General Observation - COCKROACHES IN MANHOLE285 ft. AMH - Downstream Manhole, Survey Ends - 01 0257

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.5 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    285 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (15)

DistanceCodeObservation
185.9TFA
0MWM
225.4TFC
3.5FM
0MGOCOCKROACHES IN MANHOLE
267.5TFA
283.6DAGS
0AMH01 0258
285MGOCOCKROACHES IN MANHOLE
285AMH01 0257
283.6FM
0MWL
2DAGS
147.6TFA
0MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK

Properties (7)

additional_info
SC411291
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2020-06-17T02:18:16-07:00
documentation
PRO PIPE
is_lateral_inspection
false