Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 10, 2020, 08:11 AM
  • 01 0239_01 0238_06102020_012643.mp4

Date
06/10/2020
W/O
833688
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00218
PipeID
P01284
Time
1:11 AM
Certificate
U-111-11880
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7691
Sewer Name
SOUTH PARK AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_833688_TV01204_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
12 in.
Upstream MH
01 0239
Downstream MH
01 0238
Dir. of Survey
Downstream
Length Surveyed
311.3 ft.
Total Length
311.3 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
183
O&M Index
2
O&M Quick
412L
O&M Rating
132
Overall Index
3
Overall Quick
Overall Rating
315
Pipe schematic from manhole 01 0239 to 01 0238
MH: 01 0239MH: 01 0238downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02390 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start4.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start9.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"29 ft. TBI - Tap Break-In Intruding, at 02 o'clock, -, #v, within 8 inches of joint: NO, 6", 1"59.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"89.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"98 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"110 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"136.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"139.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"169.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"189.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"193 ft. TBI - Tap Break-In Intruding, at 02 o'clock, -, #v, within 8 inches of joint: NO, 6", 2"222.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"239.5 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"259.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"281.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"293.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"309.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE309.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish309.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish311.3 ft. AMH - Downstream Manhole, Survey Ends - 01 0238311.3 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4.3 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Intruding, at 02 o'clock, -, #v, within 8 inches of joint: NO, 6", 1"

    29 ft. - Tap Break-In Intruding, at 02 o'clock, -, #v, within 8 inches of joint: NO, 6", 1"

  • Tap Break-In Intruding, at 02 o'clock, -, #v, within 8 inches of joint: NO, 6", 2"

    193 ft. - Tap Break-In Intruding, at 02 o'clock, -, #v, within 8 inches of joint: NO, 6", 2"

  • General Observation - COCKROACHES IN MANHOLE

    309.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (26)

DistanceCodeObservation
0MWL
110TFA
259.2TFA
2DAGS
311.3AMH01 0238
29TBI
311.3MGOCONNECTION AT MH 3 O'CLOCK
98TFA
309.9MGOCOCKROACHES IN MANHOLE
139.1TFA
0AMH01 0239
281.7TFA
193TBI
222.8TFA
4.3CM
239.5TBA
59.5TFA
136.5TFC
309.9CM
293.8TFC
9.7TFC
0MWM
309.9DAGS
169.9TFC
189.8TFA
89.6TFC

Properties (7)

additional_info
SC411283
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-06-10T01:11:21-07:00
documentation
PRO PIPE
is_lateral_inspection
false