Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 10, 2020, 06:20 AM
  • 01 0232_01 0036_06092020_233850.mp4

Date
06/09/2020
W/O
833688
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00218
PipeID
P01275
Time
11:20 PM
Certificate
U-111-11880
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7691
Sewer Name
SOUTH PARK AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_833688_TV01204_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
12 in.
Upstream MH
01 0232
Downstream MH
01 0036
Dir. of Survey
Downstream
Length Surveyed
301.2 ft.
Total Length
301.2 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
156
O&M Index
2
O&M Quick
412V
O&M Rating
234
Overall Index
2
Overall Quick
Overall Rating
390
Pipe schematic from manhole 01 0232 to 01 0036
MH: 01 0232MH: 01 0036downstream0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02322 ft. LFW - Lining Failure Wrinkled, from 12 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. MLC - Lining Change, Cured in place22.5 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS30.7 ft. LFW - Lining Failure Wrinkled, from 12 to 03 o'clock, within 8 inches of joint: YES, Finish69.2 ft. LFW - Lining Failure Wrinkled, from 12 to 03 o'clock, within 8 inches of joint: YES, Start297.3 ft. LFW - Lining Failure Wrinkled, from 12 to 03 o'clock, within 8 inches of joint: YES, Finish299.4 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish300.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish301.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE301.2 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 12 AND 9 O' CLOCK301.2 ft. MGO - General Observation - RUN LIST STATES MH AT 292'.301.2 ft. AMH - Downstream Manhole, Survey Ends - 01 0036

Observation photos (5)

  • Lining Failure Wrinkled, from 12 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Lining Failure Wrinkled, from 12 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Lining Change, Cured in place

    2 ft. - Lining Change, Cured in place

  • Lining Failure Wrinkled, from 12 to 03 o'clock, within 8 inches of joint: YES, Start

    69.2 ft. - Lining Failure Wrinkled, from 12 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    301.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (16)

DistanceCodeObservation
297.3LFW
301.2MGOCOCKROACHES IN MANHOLE
22.5DSZDEBRIS
0MWL
2LFW
69.2LFW
301.2MGOCONNECTIONS IN MH AT BOTH 12 AND 9 O' CLOCK
0MWM
299.4DSZ
2DAGS
300.5DAGS
30.7LFW
301.2MGORUN LIST STATES MH AT 292'.
301.2AMH01 0036
0AMH01 0232
2MLC

Properties (7)

additional_info
SC411283
custom_field_three
LIGHT GREASE/WRINKLED LINER
custom_field_two
3
customer
1
datetime
2020-06-09T23:20:58-07:00
documentation
PRO PIPE
is_lateral_inspection
false