Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 13, 2020, 09:51 AM
  • G 0114_G 0113_8132020_030533.mp4

Date
08/13/2020
W/O
0838950
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01180
PipeID
P01441
Time
2:51 AM
Certificate
U_1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1530
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
19
Purpose
Capital Improvement Program Assesment
Project
20200811MDM_JOINT_OUTFALL_G_UNIT_8
Material
RCP-CTL
Shape
Circular
Height
48 in.
Upstream MH
G 0114
Downstream MH
G 0113
Dir. of Survey
Downstream
Length Surveyed
290.3 ft.
Total Length
290.3 ft.
Structural Index
5
Structural Quick
5541
Structural Rating
29
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
33
Pipe schematic from manhole G 0114 to G 0113
MH: G 0114MH: G 0113downstream0 ft. AMH - Upstream Manhole, Survey Begins - 3:05AM0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. MWL - Water Level, 50 %of cross sectional area2 ft. MGO - General Observation - 95% MISSING TILES START2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR CORRODED & MISSING2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. MGO - General Observation - MAG COAT 5% START19.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - MISSING CORRODED AWAY REBAR105.4 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR123.7 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR202.4 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR289 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR BROKEN & MISSING289 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG289 ft. MGO - General Observation - MH CONN 9:00 ACTIVE289 ft. MGO - General Observation - MH CONN 3:00 ACTIVE289 ft. MGO - General Observation - 95% MISSING TILES FINISH289 ft. MGO - General Observation - 5% MAG COAT FINISH290.3 ft. AMH - Downstream Manhole, Survey Ends - 3:35AM

Observation photos (8)

  • General Observation - 95% MISSING TILES START

    2 ft. - General Observation - 95% MISSING TILES START

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR CORRODED & MISSING

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR CORRODED & MISSING

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - MAG COAT 5% START

    2 ft. - General Observation - MAG COAT 5% START

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - MISSING CORRODED AWAY REBAR

    19.3 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - MISSING CORRODED AWAY REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

    105.4 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

    123.7 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

    202.4 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

Observations (18)

DistanceCodeObservation
202.4SRCBROKEN MISSING REBAR
0AMH3:05AM
2MGO95% MISSING TILES START
2SRCLONG & CIRCUM REBAR CORRODED & MISSING
290.3AMH3:35AM
2SAMSEVERE AGG
0MWM
289SRCLONG & CIRCUM REBAR BROKEN & MISSING
2MGOMAG COAT 5% START
289SAMSEVERE AGG
0MWL
105.4SRCBROKEN MISSING REBAR
19.3SRCMISSING CORRODED AWAY REBAR
123.7SRCBROKEN MISSING REBAR
289MGOMH CONN 9:00 ACTIVE
289MGOMH CONN 3:00 ACTIVE
289MGO95% MISSING TILES FINISH
289MGO5% MAG COAT FINISH

Properties (6)

custom_field_three
LONG & CIRCUM REBAR CORRODED & MISSING
custom_field_two
1
customer
LACSD
datetime
2020-08-13T02:51:02-07:00
documentation
MARTIN,OLIVER 111,BARR,CASTILLO
is_lateral_inspection
false