Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 13, 2020, 06:55 AM
  • G 0115_G 0114_8122020_020157.mp4

Date
08/12/2020
W/O
0838950
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01180
PipeID
P01442
Time
11:55 PM
Certificate
U_1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1530
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
19
Purpose
Capital Improvement Program Assesment
Project
20200811MDM_JOINT_OUTFALL_G_UNIT_8
Material
RCP-CTL
Shape
Circular
Height
48 in.
Upstream MH
G 0115
Downstream MH
G 0114
Dir. of Survey
Downstream
Length Surveyed
300.8 ft.
Total Length
300.8 ft.
Structural Index
5
Structural Quick
5741
Structural Rating
39
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
43
Pipe schematic from manhole G 0115 to G 0114
MH: G 0115MH: G 0114downstream0 ft. MWM - Water Mark, 70 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:05AM0 ft. MWL - Water Level, 60 %of cross sectional area2 ft. MGO - General Observation - MISSING TILES 95% START2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR10.6 ft. MGO - General Observation - 5% MAG COAT START20.6 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CORRODED MISSING LONG & CIRCUM REBAR23.6 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR33.1 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - MISSING REBAR252.6 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR265 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR279.6 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR MISSING300.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR CORRODED & MISSINH300.2 ft. MGO - General Observation - 95% MISSING TILES FINISH300.2 ft. MGO - General Observation - MAG COAT 5% FINISH300.2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG300.8 ft. AMH - Downstream Manhole, Survey Ends - 2:40AM

Observation photos (10)

  • General Observation - MISSING TILES 95% START

    2 ft. - General Observation - MISSING TILES 95% START

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • General Observation - 5% MAG COAT START

    10.6 ft. - General Observation - 5% MAG COAT START

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CORRODED MISSING LONG & CIRCUM REBAR

    20.6 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CORRODED MISSING LONG & CIRCUM REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

    23.6 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - MISSING REBAR

    33.1 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - MISSING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

    252.6 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR

    265 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR MISSING

    279.6 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR MISSING

Observations (18)

DistanceCodeObservation
10.6MGO5% MAG COAT START
23.6SRCBROKEN MISSING REBAR
265SRCBROKEN MISSING REBAR
33.1SRCMISSING REBAR
0MWM
20.6SRCCORRODED MISSING LONG & CIRCUM REBAR
300.2SRCLONG & CIRCUM REBAR CORRODED & MISSINH
0AMH2:05AM
0MWL
300.8AMH2:40AM
279.6SRCLONG & CIRCUM REBAR MISSING
300.2MGO95% MISSING TILES FINISH
252.6SRCBROKEN MISSING REBAR
2MGOMISSING TILES 95% START
300.2MGOMAG COAT 5% FINISH
2SAMSEVERE AGG
2SRCCIRCUM REBAR
300.2SAMSEVERE AGG

Properties (6)

custom_field_three
LONG & CIRCUM REBAR CORRODED & MISSING
custom_field_two
1
customer
LACSD
datetime
2020-08-12T23:55:09-07:00
documentation
MARTIN,OLIVER 111,BARR,CASTILLO
is_lateral_inspection
false