Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 12, 2020, 06:44 AM
  • G 0118_G 0117_8112020_010003.mp4

Date
08/11/2020
W/O
0838950
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01180
PipeID
P01445
Time
11:44 PM
Certificate
U_1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1527
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
19
Purpose
Capital Improvement Program Assesment
Project
20200811MDM_JOINT_OUTFALL_G_UNIT_8
Material
RCP-CTL
Shape
Circular
Height
48 in.
Upstream MH
G 0118
Downstream MH
G 0117
Dir. of Survey
Downstream
Length Surveyed
358.9 ft.
Total Length
358.9 ft.
Structural Index
5
Structural Quick
5741
Structural Rating
39
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
5
Overall Quick
Overall Rating
44
Pipe schematic from manhole G 0118 to G 0117
MH: G 0118MH: G 0117downstream0 ft. MWM - Water Mark, 90 %of cross sectional area0 ft. MWL - Water Level, 80 %of cross sectional area0 ft. MGO - General Observation - MH CONN 9:00 OPEN STOPLOG IN PLACE0 ft. AMH - Upstream Manhole, Survey Begins - 12:55AM2 ft. MGO - General Observation - 100% MISSING TILES2 ft. MGO - General Observation - MAG COAT 10% START2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG17.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR POSSIBLE CORRODED AND MISSING33 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR34.9 ft. MGO - General Observation - 1 ROW TILES IN PLACE45.6 ft. MGO - General Observation - 80% TILES IN PLACE START54.2 ft. MGO - General Observation - 0% MISSING TILES START63.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR69.9 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR88.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR96.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR124.4 ft. MGO - General Observation - MISSING TILES 100% START141.3 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR CORRODED MISSING161.8 ft. MGO - General Observation - TILES 60% MISSING START188.6 ft. MGO - General Observation - 100% MISSING TILES213.8 ft. MGO - General Observation - 1 SECTION TILES IN PLACE240.2 ft. MGO - General Observation - 1 SECTION TILES IN PLACE272.4 ft. MGO - General Observation - 2 ROWS TILES IN PLACE358.3 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG358.3 ft. MGO - General Observation - 10% MAG COAT FINISH358.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Finish - CIRCUM REBAR CORRODED & MISSING358.3 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Finish - LONG REBAR CORRODED & MISSING358.3 ft. MGO - General Observation - 100% MISSING TILES FINISH358.9 ft. AMH - Downstream Manhole, Survey Ends - 2:55AM

Observation photos (13)

  • General Observation - 100% MISSING TILES

    2 ft. - General Observation - 100% MISSING TILES

  • General Observation - MAG COAT 10% START

    2 ft. - General Observation - MAG COAT 10% START

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR POSSIBLE CORRODED AND MISSING

    17.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR POSSIBLE CORRODED AND MISSING

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    33 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • General Observation - 80% TILES IN PLACE START

    45.6 ft. - General Observation - 80% TILES IN PLACE START

  • General Observation - 0% MISSING TILES START

    54.2 ft. - General Observation - 0% MISSING TILES START

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR

    63.2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR

    69.9 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR

    88.1 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    96.2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • General Observation - MISSING TILES 100% START

    124.4 ft. - General Observation - MISSING TILES 100% START

  • Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR CORRODED MISSING

    141.3 ft. - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR CORRODED MISSING

Observations (29)

DistanceCodeObservation
2MGO100% MISSING TILES
161.8MGOTILES 60% MISSING START
96.2SRCCIRCUM REBAR
213.8MGO1 SECTION TILES IN PLACE
34.9MGO1 ROW TILES IN PLACE
54.2MGO0% MISSING TILES START
141.3SRCLONG REBAR CORRODED MISSING
2MGOMAG COAT 10% START
88.1SRCCORRODED MISSING REBAR
358.3SAMSEVERE AGG
69.9SRCCORRODED MISSING REBAR
2SAMSEVERE AGG
358.3MGO10% MAG COAT FINISH
45.6MGO80% TILES IN PLACE START
0MWM
0MWL
240.2MGO1 SECTION TILES IN PLACE
188.6MGO100% MISSING TILES
358.3SRCCIRCUM REBAR CORRODED & MISSING
272.4MGO2 ROWS TILES IN PLACE
358.3SRCLONG REBAR CORRODED & MISSING
0MGOMH CONN 9:00 OPEN STOPLOG IN PLACE
124.4MGOMISSING TILES 100% START
63.2SRCCORRODED MISSING REBAR
33SRCCIRCUM REBAR
358.9AMH2:55AM
358.3MGO100% MISSING TILES FINISH
0AMH12:55AM
17.6SRCCIRCUM REBAR POSSIBLE CORRODED AND MISSING

Properties (6)

custom_field_three
LONG & CIRCUM REBAR CORRODED & MISSING
custom_field_two
1
customer
LACSD
datetime
2020-08-11T23:44:54-07:00
documentation
MARTIN,OLIVER 111,BARR,CASTILLO
is_lateral_inspection
false