Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 28, 2020, 08:20 AM
  • G 0125_G 0124_07282020_013638.mp4

Date
07/28/2020
W/O
838806
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01180
PipeID
P25030
Time
1:20 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7929
Sewer Name
JOINT OUTFALL G - UNIT 8
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
21
Purpose
Routine Assessment
Project
WO_838806_TV01004_JUL2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
G 0125
Downstream MH
G 0124
Dir. of Survey
Downstream
Length Surveyed
255.1 ft.
Total Length
255.1 ft.
Structural Index
2
Structural Quick
2I00
Structural Rating
100
O&M Index
2
O&M Quick
2I00
O&M Rating
100
Overall Index
2
Overall Quick
Overall Rating
200
Pipe schematic from manhole G 0125 to G 0124
MH: G 0125MH: G 0124downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - G 01252 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start253 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish253 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish255 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE255.1 ft. AMH - Downstream Manhole, Survey Ends - G 0124

Observations (10)

DistanceCodeObservation
253DAGS
0MWM
253SSS
2DAGS
2SSS
255MGOCONN @ MH 3 O'CLOCK/ACTIVE
0MWL
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
0AMHG 0125
255.1AMHG 0124

Properties (8)

additional_info
SC411789
custom_field_three
NO SEVERE DEFECTS
custom_field_two
3
customer
1
datetime
2020-07-28T01:20:41-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
38026