Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 28, 2020, 09:28 AM
  • G 0122_G 0121_07282020_024228.mp4

Date
07/28/2020
W/O
838806
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01180
PipeID
P25027
Time
2:28 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7931
Sewer Name
JOINT OUTFALL G - UNIT 8
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
21
Purpose
Routine Assessment
Project
WO_838806_TV01004_JUL2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
G 0122
Downstream MH
G 0121
Dir. of Survey
Downstream
Length Surveyed
226.3 ft.
Total Length
226.3 ft.
Structural Index
3
Structural Quick
3H2H
Structural Rating
220
O&M Index
2
O&M Quick
2H00
O&M Rating
92
Overall Index
2
Overall Quick
Overall Rating
312
Pipe schematic from manhole G 0122 to G 0121
MH: G 0122MH: G 0121downstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - G 01220 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/UNKNOWN0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAR - Deposits Attached Ragging, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start224 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish224 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish224 ft. DAR - Deposits Attached Ragging, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish224 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish226.3 ft. AMH - Downstream Manhole, Survey Ends - G 0121

Observations (14)

DistanceCodeObservation
0MWL
0MWM
224CM
0AMHG 0122
2DAGS
224SSS
2CM
2SSS
0MGOCONN @ MH 9 O'CLOCK/UNKNOWN
226.3AMHG 0121
224DAR
2DAR
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
224DAGS

Properties (8)

additional_info
SC411791
custom_field_three
NO SEVERE DEFECTS
custom_field_two
3
customer
1
datetime
2020-07-28T02:28:08-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
38026