- Date
- 07/07/2020
- W/O
- 838907
- Weather
- Dry
- Operator/Surveyor
- J. BUENROSTRO
- Sewer ID
- Z00705
- PipeID
- P14372
- Time
- 12:57 AM
- Certificate
- U-715-07000770
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K7818
- Sewer Name
- SOUTH PLANT OUTFALL TRUNK
- City
- WHITTIER
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 10
- Purpose
- Routine Assessment
- Project
- RFIR_WO_838907_TV18194_JUL2020
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 21 in.
- Width
- 21 in.
- Upstream MH
- 18 0518
- Downstream MH
- 18 0517
- Dir. of Survey
- Downstream
- Length Surveyed
- 345.1 ft.
- Total Length
- 345.1 ft.
- Structural Index
- 4
- Structural Quick
- 4M00
- Structural Rating
- 272
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 4
- Overall Quick
- —
- Overall Rating
- 272
Pipe schematic from manhole 18 0518 to 18 0517 Observation photos (4)

2.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

9.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

12.2 ft. - Repair Patch, from 11 to 01 o'clock, within 8 inches of joint: YES - EXTERNAL

17.4 ft. - Repair Patch, from 12 to 01 o'clock, within 8 inches of joint: NO - EXTERNAL