Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 10, 2020, 07:32 AM
  • _29 0499_07102020_010310.mp4

Date
07/10/2020
W/O
838812
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00985
PipeID
P24547
Time
12:32 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7325
Sewer Name
CHERRY AVENUE SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
02
Purpose
Routine Assessment
Project
RFIR_WO_838812_TV29116_JUL2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0499
Dir. of Survey
Upstream
Length Surveyed
322.4 ft.
Total Length
322.4 ft.
Structural Index
2
Structural Quick
2111
Structural Rating
3
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
9
Pipe schematic from manhole 29 0499 to unknown
MH: 29 0499MH: upstream0 ft. ACOM - Cleanout Mainline, Survey Ends3.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"6.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"60.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"63.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"115.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"118.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"174 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"176.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"235.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"238.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"276.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish290.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"293 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"297.9 ft. JOM - Joint Offset Medium302.9 ft. MWLS - Water Level, Sag in pipe, 20 %of cross sectional area, Finish308.9 ft. MWLS - Water Level, Sag in pipe, 20 %of cross sectional area, Start320.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start322.4 ft. MWM - Water Mark, 55 %of cross sectional area322.4 ft. MWL - Water Level, 0 %of cross sectional area322.4 ft. AMH - Downstream Manhole, Survey Begins - 29 0499322.4 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Joint Offset Medium

    24.5 ft. - Joint Offset Medium

Observations (22)

DistanceCodeObservation
32TFC
145.7TFC
2.1DAGS
19.5MWLS
203.9TFC
13.5MWLS
315.9TFC
46.1DAGS
0MWM
84TFC
0MWL
206.7TFC
148.4TFC
318.5TFC
0AMH29 0499
86.8TFC
29.4TFC
258.9TF
261.6TFC
322.4ACOM
0MGOCONNECTION AT MH 3 OCLOCK
24.5JOM

Properties (7)

additional_info
SC411317
custom_field_three
MULTIPLE FRACTURE
custom_field_two
3
customer
1
datetime
2020-07-10T00:32:36-07:00
documentation
PRO PIPE
is_lateral_inspection
false