Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 10, 2020, 06:51 AM
  • 29 0485_29 0484_07102020_001451.mp4

Date
07/09/2020
W/O
838812
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00789
PipeID
P24531
Time
11:51 PM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7325
Sewer Name
CHERRY AVENUE TRUNK
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
02
Purpose
Routine Assessment
Project
RFIR_WO_838812_TV29116_JUL2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0485
Downstream MH
29 0484
Dir. of Survey
Downstream
Length Surveyed
348.2 ft.
Total Length
348.2 ft.
Structural Index
4
Structural Quick
4300
Structural Rating
12
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
12
Pipe schematic from manhole 29 0485 to 29 0484
MH: 29 0485MH: 29 0484downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 OCLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 29 04857.6 ft. FM - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES10.9 ft. FM - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES78.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"128.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"177 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"226.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"278.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"324.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"339 ft. FM - Fracture Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES348.2 ft. AMH - Downstream Manhole, Survey Ends - 29 0484

Observation photos (3)

  • Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

    7.6 ft. - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

    10.9 ft. - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES

    339 ft. - Fracture Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES

Observations (14)

DistanceCodeObservation
226.3TFC
0MWL
339FM
0MWM
278.7TFC
324.4TFC
0MGOCONNECTION AT MH 9 OCLOCK
348.2AMH29 0484
78.9TFC
128.8TFC
10.9FM
0AMH29 0485
7.6FM
177TFC

Properties (7)

additional_info
SC411317
custom_field_three
MULTIPLE FRACTURE
custom_field_two
3
customer
1
datetime
2020-07-09T23:51:46-07:00
documentation
PRO PIPE
is_lateral_inspection
false